| SKU | 7100412533 |
|---|---|
| Legacy SKU | 98044111270 |
| UPC | 00068060016676 |
| Product Number | EBI 4R |
3M Fire Barrier Electrical Box Inserts are a flexible, one-piece fire-rated intumescent insert used to protect electrical boxes by adhering to the inside the box. When exposed to fire, the insert expands to fill up the box preventing the spread of fire and limiting temperature rise.
- Protection of membrane penetrations for listed metallic boxes
- Tested in accordance with ASTM E814 (UL 1479) (Certified as a Wall Opening Protective Material, UL Category CLIV).
- STC rating of 62 when tested in a STC 62 rated wall assembly
- Flexible
- Convenient slits for access to wiring
- Great for new construction and retro fit applications
Product Dimensions |
Imperial | Metric |
| Weight | 0.291 lbs | |
|---|---|---|
| Width | 6 in | |
| Length | 6 in | |
| Height | 0.66693 in |
Shipping Dimensions |
|
| Weight | 2.1 lb |
|---|---|
| Length | 6.6248 in |
| Width | 4.56299 in |
| Height | 6.8748 in |
| Color | Red |
|---|
The 3M Fire Barrier Electrical Box Insert represents a specialized fire-safety solution engineered to mitigate fire propagation through wall assemblies that have been penetrated by electrical boxes. This product is specifically designed for integration into both one-hour and two-hour fire-rated gypsum wall systems, where electrical penetrations would otherwise create potential pathways for flames and smoke to breach the fire-resistant integrity of the wall assembly.
How It WorksThe insert operates through a thermally-activated expansion mechanism that engages when exposed to elevated temperatures during a fire event. As heat is applied, the material undergoes a controlled expansion process that effectively seals the internal airspace within the electrical box, eliminating gaps that could allow flames, smoke, or hot gases to pass through. Additionally, the insert develops a protective char layer on its surface, which serves as a thermal barrier that actively resists further fire advancement and helps maintain the structural integrity of the wall system during critical early stages of a fire incident.
Applications- One-hour rated gypsum wall assemblies with metallic electrical box penetrations
- Two-hour rated gypsum wall assemblies with metallic electrical box penetrations
- Fire-rated wall systems requiring electrical outlet or switch box installation